What is the pipe outside your wall costing you?
If you have a heat pump, there is a run of pipe between the outdoor unit and your house. When that pipe is bare or thinly wrapped, it sheds heat into the garden all winter, and your heat pump quietly pays to replace it. Drag the slider and watch what the insulation choice is worth. The calculator runs entirely in your browser, and what you enter stays there unless you ask us for a reading below.
Insulating this run is worth
£18 a year
about £266 over fifteen years
On a deliberately modest 1,800-hour season. Across the 107,336 real Nottingham homes in the city view, the median modelled heating year is 3,592 hours, so a real home's figure is often around double this.
One thing changes at a time; everything else holds still.
Left bare
£26 / year
314 kWh of lost heat
With 13 mm of insulation
£8 / year
97 kWh of lost heat
Your numbers
Your pipe, from above. The blue ring is the insulation you chose.
The first few millimetres do most of the work. After that, each one helps a little less.
The run the calculation does model, worked in full
Your home has a second run: the hot water cylinder's primary circuit, the one the national calculation does model. Below, the same insulation choice on that run goes through the complete calculation, a full year, hour by hour, for a typical home. The calculation runs the heat pump itself, so no efficiency guess is needed, and the circuit's duty comes from the modelled year itself.
On the primary circuit, the full calculation says this choice saves
£13 a year
52 kWh of electricity, at your rate, no efficiency assumption
On the outdoor run above, the formula says
£18 a year
with its flat 1,800-hour season and your efficiency setting
The two runs answer differently because their duties differ. The primary circuit works only while the cylinder charges, a few hundred hours a year, counted exactly by the calculation. The outdoor run sheds heat through the whole heating season, 2,098 modelled hours in this home, and the calculation never looks at it. A single formula answers a typical home; a reading answers yours.
nearest modelled thickness: 15 mm.
Precomputed from the full calculation; the run itself is checked between two separate implementations of the method within 1 kWh.
What the official calculation sees of this loss: nothing.
The run between your outdoor unit and the house sits on the emitter side, and the national calculation models no pipework loss there at all. Where pipework is in scope (the hot water cylinder's primary circuit), the insulation thickness is declared, never verified. Every pound on this page is invisible to the compliance figures your home is judged by. We implement the method; that is how we can say precisely where it looks away.