Skip to content

TP-06: Ventilation and Infiltration

Technical reference for the HEM ventilation and infiltration methodology, covering air change rates, mechanical ventilation, and heat recovery.

Overview

Ventilation and infiltration determine the rate at which outdoor air enters and conditioned air leaves a dwelling. This air exchange drives a heat loss (or gain) that, alongside fabric losses, determines the space heating demand.

The calculation follows Method 1 of BS EN 16798-7:2017, which uses a pressure-based airflow network to compute mass flow rates through each airflow path: envelope leaks, purpose-built vents, openable windows, combustion appliances, and mechanical ventilation systems. The internal reference pressure is solved iteratively to satisfy mass balance at each timestep.

The resulting ventilation heat transfer coefficient W/K enters the zone heat balance directly, coupling the ventilation calculation to the space heating demand solver.

Inputs

ParameterSymbolUnitDescription
Zone volumeInternal volume of the ventilation zone
Ventilation zone heightmFloor-to-ceiling height of the ventilation zone
Ventilation zone base heightmHeight of the zone floor above ground level
AltitudemAltitude of the dwelling above sea level
Cross-ventilation flagWhether cross-ventilation is possible (boolean)
Shield classExposure to wind: Open, Normal, or Shielded
Terrain classSite terrain: OpenWater, OpenField, Suburban, or Urban
Average roof pitchdegreesArea-weighted average pitch of all roof elements
Air permeability test pressurePaReference pressure difference from pressurisation test (typically 50 Pa)
Air permeability test resultm³/(h·m²)Measured air flow rate at test pressure per unit envelope area
Envelope areaReference area of the envelope airtightness index
Facade areaTotal surface area of vertical facades
Roof areaTotal surface area of the roof
Window opening areaMaximum opening area of each window
Window free area heightmHeight of the window free area
Window mid-heightmMid-height of the window airflow path
Vent equivalent areacm²Equivalent area of each purpose-built vent
Vent reference pressurePaReference pressure difference for the vent
Design outdoor air flow ratem³/hDesign mechanical ventilation flow rate
Specific fan powerSFPW/(l/s)Fan power per unit flow rate, inclusive of in-use factors
MVHR efficiencyHeat recovery efficiency (0 to 1)
Wind speed at 10 mm/sMeteorological wind speed from climate data
Wind directiondegreesClockwise from North
External air temperature°CFrom climate data
Internal air temperature°CZone air temperature (from heat balance solver)

Calculation

Air Density Correction

Air density is adjusted for the site altitude above sea level:

where kg/m³ is the reference air density at sea level and 20 °C.

At a given temperature (in Kelvin), the local air density is:

where K.

Wind Speed at Zone Level

The meteorological wind speed is corrected for terrain roughness to obtain the wind speed at the building zone level:

where:

  • is the roughness coefficient at the building site
  • is the topography coefficient at the building site (default 1.0)
  • is the roughness coefficient at the meteorological station (default 1.0)
  • is the topography coefficient at the meteorological station (default 1.0)

Terrain Roughness Coefficient

The roughness coefficient depends on terrain class and height of the airflow path :

where is clamped to a minimum value . The terrain parameters are:

Terrain class (m) (m)
OpenWater0.170.012
OpenField0.190.054
Suburban0.220.38
Urban0.241.016

Pressure Difference at an Airflow Path

The pressure difference between exterior and interior at a given airflow path height drives airflow through each opening. From BS EN 16798-7, Equations 4, 5, and 6:

where:

  • is the internal reference pressure (Pa), solved iteratively
  • is the wind pressure coefficient for the airflow path
  • m/s² is the gravitational acceleration
  • and are external and zone air temperatures in Kelvin

Wind Pressure Coefficients

Wind pressure coefficients are determined from BS EN 16798-7, Table B.7. The coefficient depends on facade direction (windward, leeward, or neither), shield class, height, and whether cross-ventilation is possible.

Facade Direction

For elements with pitch 60° (walls), the facade direction is determined by comparing the element orientation with the wind direction:

  • Windward: orientation difference 60°
  • Neither: orientation difference between 60° and 120°
  • Leeward: orientation difference 120°

For elements with pitch < 60° (roofs), further classification applies when cross-ventilation is possible: Roof10 (pitch < 10°), Roof10_30 (10° to 30°), and Roof30 (30° to 60°).

Cross-Ventilation Coefficients

When cross-ventilation is possible (), the wind pressure coefficients for walls vary with height and shield class:

HeightShieldWindwardLeeward
mOpen0.50
mNormal0.25
mShielded0.05
mOpen0.65
mNormal0.45
mShielded0.25
mOpen0.80

Non-Cross-Ventilation Coefficients

When cross-ventilation is not possible, reduced coefficients apply: windward = 0.05, leeward = , roof = 0, neither = 0.

Airflow Through Envelope Leaks

Envelope leakage is distributed across five notional leak paths (BS EN 16798-7, Table B.12):

  1. Windward facade at 0.25
  2. Leeward facade at 0.25
  3. Windward facade at 0.75
  4. Leeward facade at 0.75
  5. Roof at

Leakage Coefficient

The overall leakage coefficient is derived from the pressurisation test result:

where is the flow exponent for leaks (BS EN 16798-7, Section B.3.3.14).

This is distributed between facades and roof in proportion to their areas:

Each facade leak path receives 0.25 of the facade leakage coefficient (four paths share the facade leakage), while the single roof path receives the full roof leakage coefficient.

Leak Airflow

The volume flow rate through each leak path is (Equation 62):

Airflow Through Vents

Purpose-built vents (trickle vents, air bricks) are modelled as openings with adjustable position (0 = closed, 1 = fully open).

Vent Flow Coefficient

The airflow coefficient is calculated from the equivalent area (Equation 59):

where:

  • is the discharge coefficient (BS EN 16798-7, Section B.3.2.1)
  • is the flow exponent (BS EN 16798-7, Section B.3.2.2)
  • is the effective opening area

Vent Airflow

The volume flow rate through each vent is (Equation 58):

Airflow Through Windows

Openable windows are modelled using Section 6.4.3.5 of BS EN 16798-7. Each window may be divided into multiple parts to capture vertical pressure gradients across the window height.

Window Opening Free Area

The window opening free area depends on the opening ratio (Equation 40):

Windows are treated as closed () if no window-opening control is defined or if the control signal is off.

Window Flow Coefficient

The flow coefficient for a window is (Equation 54):

where:

  • is the window discharge coefficient (BS EN 16798-7, Section B.3.2.1)
  • is the window flow exponent (BS EN 16798-7, Section B.3.2.2)

Window Part Heights

For a window divided into divisions, the height for pressure difference calculation at the -th part is (Equation 55):

Window Part Airflow

The airflow through each window division is (Equation 53):

Airflows through all window parts are summed to give total inflow and outflow through the window (Equations 56 and 57).

Combustion Appliances

Combustion appliances that draw room air for combustion create an additional extract airflow. The volume flow rate is (Equation 35):

where:

  • is the operation signal (0 = off, 1 = on)
  • is the appliance system factor (Table B.2)
  • is the fuel flow factor (Table B.3)
  • is the fuel input power kW

The appliance system factor depends on the combustion air supply and flue gas exhaust arrangements:

Supply situationExhaust situation
Outside airAny0
Room airInto room0
Room airInto separate duct1

Fuel flow factors from Table B.3:

FuelAppliance type
WoodOpen fireplace2.8
GasClosed with fan0.38
GasOpen gas flue balancer0.78
GasOpen gas fire / kitchen stove3.35
OilClosed fire0.32
CoalClosed fire0.52

This flow is treated as outgoing (extract) from the zone (Equations 37 and 38).

Mechanical Ventilation

Mechanical ventilation systems provide controlled air supply and/or extraction. The model supports five system types:

  • MVHR (Mechanical Ventilation with Heat Recovery): balanced supply and extract with heat recovery
  • Centralised continuous MEV (Mechanical Extract Ventilation): extract only, continuous operation
  • Decentralised continuous MEV: extract only, continuous, individual fans per wet room
  • Intermittent MEV: extract only, operating on a timed schedule
  • PIV (Positive Input Ventilation): supply only

Required Outdoor Air Flow Rate

The design outdoor air flow rate is adjusted for system and control factors (Equation 9):

where:

  • (Table B.4, residential default)
  • (Table B.5)
  • (Section B.3.3.7, assuming perfect mixing)

Air Flow at Terminal Devices

The required supply and extract flow rates at the air terminal devices depend on system type (Equations 10 to 17):

System type
MVHR
MEV (all types)0
PIV0

The actual flow rates to the zone are scaled by the operational fraction :

For continuous systems (MVHR, centralised and decentralised MEV), . For intermittent MEV, is determined by the control schedule.

Heat Recovery

For MVHR systems, the effective heat recovery saving is represented as a reduction in the incoming air flow rate rather than a supply temperature increase. This avoids coupling the heat recovery calculation to the internal temperature solver:

This effective saving is subtracted from the total incoming mass flow rate when computing the ventilation heat transfer coefficient.

Fan Energy

Fan power is calculated from the specific fan power and the design flow rate, apportioned to the zone by volume fraction:

where is in watts, the factor of 3600 converts m³/h to m³/s, and 1000 converts m³ to litres. Fan energy per timestep is:

where is the timestep duration in hours.

For MVHR, fan energy is split equally between supply and extract fans. For MEV systems, all fan energy is attributed to the extract fan. For PIV, all fan energy is attributed to the supply fan. The supply fan energy contributes to internal heat gains within the zone.

Mass Balance and Internal Reference Pressure

At each timestep, the internal reference pressure is determined by solving the mass balance equation (Equation 67):

The total incoming and outgoing mass flow rates include contributions from all airflow paths:

Volume and mass flow rates are related by:

where incoming air is at external temperature and outgoing air at zone temperature (Equations 65 and 66).

The solver uses Brent's method to find the root of the mass balance equation, expanding the search interval progressively through the sequence 1, 5, 10, 15, 20, 40, 50, 100, 200 Pa around an initial guess until a valid bracket is found.

Vent Opening Control

When minimum and maximum air change rate limits are specified, the vent opening ratio is adjusted to bring the air change rate within bounds.

The procedure is:

  1. Calculate ACH at the current from the previous timestep.
  2. If ACH is within , retain the current .
  3. If ACH is below , check whether fully opening vents () can reach the minimum. If not, set . Otherwise, find the that achieves .
  4. If ACH exceeds , check whether fully closing vents () can reach the maximum. If not, set . Otherwise, find the that achieves .

The target is found using golden section minimisation on , minimising the residual:

The small gradient term prevents the solver from stalling on flat regions at low vent openings where leakage and mechanical flows dominate.

Ventilation Heat Transfer Coefficient

The total incoming volume flow rate, after accounting for heat recovery savings, is converted to an air change rate:

where is in m³/h and is the zone volume.

The ventilation heat transfer coefficient is then:

where:

  • kg/m³
  • J/(kg·K) is the specific heat capacity of air
  • The factor of 3600 converts m³/h to m³/s

is in W/K and represents the rate of heat loss per degree temperature difference between the zone and the external air.

Ductwork Heat Loss

For MVHR systems, ductwork connecting the heat recovery unit to the building envelope introduces additional heat losses. Ductwork insulation is modelled per ISO 12241:2022 for steady-state radial heat flow.

Duct Thermal Resistance

Each duct has three resistances in series: internal surface, insulation, and external surface.

Circular ducts:

where:

  • is the internal diameter m
  • is the outer diameter including insulation m
  • is the thermal conductivity of the insulation W/(m·K)
  • is the insulation thickness m

Rectangular ducts:

where:

  • is the internal perimeter m
  • is the external perimeter including insulation m

All linear resistances have units of K·m/W. The heat transfer coefficients are:

SurfaceConditionValue W/(m²·K)Source
InternalAir flow ~3 m/s15.5CIBSE Guide C, Table 3.25
ExternalReflective (low emissivity)5.7CIBSE Guide C, Table 3.25
ExternalNon-reflective (high emissivity)10.0CIBSE Guide C, Table 3.25

Duct Heat Loss

The heat loss through a duct of length is:

where is the temperature of the air inside the duct and is the temperature of the environment surrounding the duct.

MVHR Duct Heat Loss by Segment

An MVHR system has four duct segments: intake, supply, extract, and exhaust. Whether a duct segment contributes to the dwelling heat loss depends on the location of the MVHR unit (inside or outside the thermal envelope).

MVHR unit outside the thermal envelope:

SegmentAir temperature in ductSurrounding tempHeat loss
Intake0 (no temperature difference)
SupplyStandard duct heat loss
ExtractDuct heat loss
Exhaust0 (no temperature difference)

MVHR unit inside the thermal envelope:

SegmentAir temperature in ductSurrounding tempHeat loss
Supply (approx.)0 (no temperature difference)
Extract0 (no temperature difference)
IntakeDuct heat loss
ExhaustStandard duct heat loss

The heat recovery efficiency modifies certain duct losses because the thermal benefit of recovered heat is proportional to the efficiency.

Outputs

QuantitySymbolUnitDescription
Air changes per hourh⁻¹Effective air change rate for the zone
Ventilation heat transfer coefficientW/KHeat loss rate per degree temperature difference
Internal reference pressurePaSolved internal pressure satisfying mass balance
Vent opening ratioOptimal vent position (0 = closed, 1 = open)
Supply fan gainsWInternal heat gain from supply fan operation
Fan energy consumptionkWhTotal fan energy per timestep
Ductwork heat lossWHeat loss through MVHR ductwork

Assumptions

  • Flow exponents are fixed at (windows), (vents), and (leaks), per BS EN 16798-7.
  • Discharge coefficients are for windows and for vents and air terminal devices, per BS EN 16798-7, Section B.3.2.1.
  • The ventilation zone is modelled as a single well-mixed volume with ventilation effectiveness .
  • The control factor and system factor are fixed defaults for residential buildings (Tables B.4 and B.5).
  • Topography coefficients at both the building site and the meteorological station default to 1.0.
  • Heat recovery is represented as an effective reduction in incoming air flow rather than a supply temperature increase. This avoids coupling the MVHR calculation to the zone temperature solver.
  • MVHR supply and extract are assumed to be perfectly balanced at equal flow rates.
  • Duct internal heat transfer coefficient is fixed at 15.5 W/(m²·K), corresponding to air velocity of approximately 3 m/s.
  • Combustion appliance fuel input power and operational status are provided externally; no combustion modelling is performed within this module.

Cross-references